Radiator BTU calculator

A double bedroom of 4 × 3.5 m with a 2.4 m ceiling needs about 4,614 BTU (1,352 W) of radiator output in a typical double-glazed home.

metres
metres
metres

Most modern rooms are about 2.4 m. Older houses are often higher.

Walls with the outside on the other side, not walls to another room.

Radiator output needed7,534 BTU
In watts
2,208 W
Room volume
48.0 m³

5 × 4 m room, 2.4 m high, including a 15% margin.

Includes a 15% margin. Radiator outputs are usually quoted at ΔT50, which suits most gas boilers. For a heat pump, you will need bigger radiators: ask your installer.

BTU for common rooms

Double glazed, cavity walls, two outside walls, 2.4 m ceilings.

RoomSizeBTUWatts
Small bedroom3 × 2.5 m2,472725
Double bedroom4 × 3.5 m4,6141,352
Living room5 × 4 m7,5342,208
Kitchen4 × 3 m3,390994
Bathroom2.5 × 2 m2,119621

What changes the heat a room needs

Each choice raises or lowers the starting figure for the room.

FactorOptionChange
WindowsSingle glazed+40%
WindowsTriple glazed-15%
Type of homeModern new build-30%
Type of homeOlder, poorly insulated+20%
Type of homeVictorian or pre-1920s+50%
Outside wallsOne-15%
Outside wallsThree+15%
Outside wallsFour+30%
FacingNorth+15%
FacingSouth-10%

How we calculate this

We follow the method published by QS Supplies. The room’s volume is multiplied by a heat rate for its type: 45 W per m³ for bathrooms, 40 for living rooms, 35 for bedrooms and 30 for kitchens, where cooking adds heat.

We then adjust for windows, insulation, outside walls and which way the room faces, add a 15% margin and convert watts to BTU. For north-facing rooms, QS Supplies suggests 10 to 15% more; we use 15% so the radiator isn’t too small.

This is a quick estimate for choosing a radiator. For a new heating system or a heat pump, an installer should do a full heat loss calculation.

Watts = length × width × height × heat rate × adjustments × 1.15BTU = watts × 3.412

Questions people ask

How many BTU do I need per square metre?

It depends on the room and ceiling height, but for a typical double-glazed living room with a 2.4 m ceiling it is roughly 380 BTU per square metre. Bathrooms need more, kitchens less.

What is the difference between BTU and watts?

Both measure heat output. One watt is about 3.412 BTU per hour, so a 1,000 W radiator gives about 3,400 BTU.

Can I use two radiators instead of one big one?

Yes. Add their outputs together. Two smaller radiators on different walls can heat a large or L-shaped room more evenly.

Do I need bigger radiators with a heat pump?

Usually. Heat pumps run the water cooler than a gas boiler, so a radiator gives out less heat. Radiator outputs quoted at ΔT50 assume boiler temperatures. Your installer will size them for you.